EN 17037 §4.2 — View out

Part of EN 17037:2018. See that page for legal status.

Requirement

Assessed for the position(s) of likely occupants. Three sub-criteria:

Sub-criterionMinimumMediumHigh
Horizontal sight angle (width of view)≥ 14°≥ 28°≥ 54°
Outside distance of the view≥ 6.0 m≥ 20.0 m≥ 50.0 m
Number of view layers visible (sky / landscape / ground), over ≥ 75 % of the utilized arealandscape layer onlylandscape + one more layerall three layers

The overall rating for a space is the lowest of the three sub-criteria ratings.

This is independent of the national codes' own view-out rules where they exist — e.g. Denmark's BR18 §378 is a separate functional requirement, not based on this criterion.

Calculation setup

Assessed from reference points within the utilized area, not the daylight reference plane used for daylight provision. See Annex C of the standard for the reference-point and verification method.