Norway — TEK17 §13-7

Mandatory. TEK17 (Byggteknisk forskrift) is the regulation under the Norwegian Planning and Building Act. Daylight is covered by §13-7 Lys. The regulation states a functional requirement; the numeric criteria below are the pre-accepted performance levels (preaksepterte ytelser) in the official guidance (veiledning) from the Norwegian Building Authority (DiBK).

Requirement

ItemValue
MetricAverage daylight factor (DF) per room
ThresholdAverage DF ≥ 2.0 % in the room
Simplified alternativeGlazing area Ag ≥ 0.07 · ABRA / LT (0.10 · ABRA for leisure housing/fritidsbolig), where ABRA is the room's usable floor area and LT the glass's light transmittance
Assessment levelPer room, for rooms for lasting stay (rom for varig opphold)
Calculation methodFollows NS-EN 17037
note

Older guidance referred to a light-opening / NS 3940 area calculation. NS 3940 is the Norwegian standard for measuring areas and volumes of buildings — it is not a daylight method. The daylight factor calculation itself follows NS-EN 17037.

Calculation setup

ParameterValueNotes
Reference plane height0.85 m above floorFrom NS-EN 17037
Grid spacingp = 0.5 · 5log₁₀(d) mNS-EN 17037 formula; d = longest room dimension when the length/width ratio is 0.5–2, otherwise the shortest
Wall offset (excluded border)0.5 mNS-EN 17037
Sky modelCIE standard overcast sky

Reflectances are not stated in TEK17/veiledning; see Reflectance for the values LUX uses.

How LUX handles it

Status: ✅ Supported in LUX Live v0.3.0.

LUX has a Norway mode: it reports the average DF per room and flags each room green (≥ 2.0 %) or red. Average DF per room is already part of the LUX output, so this is a reporting layer on the existing computation.